Fan coil units archive

SF-85DS

  • Indoor duct unit
  • Cooling capacity 5,0kW
  • Heating capacity 7,6kW
  • Low noise
  • Wired (standard) and remote controller (optional)
  • Outdoor unit is separate product
Air Flow Volume - 850 m3 / h
Air flow volume - 500 CFM
External statics pressure - 30 Pa
Capacity Cooling 5040 W
Capacity Heating 7560 W
Row of cooling / heating coil - 3 -
Power System Input 87,0 W
Water System Water Flow Volume 0,91 m3 / h
Water System Water Flow Volume 4 gal / min
Water System Pressure Drop 30 kPa
Water System Pressure Drop 9,8 Ft - WG
Coil Face area 0,167 m2
Coil Face velocity 1,41 m/s
Motor Type Isolation E Capacitor startup three-speed motor -
Motor Quantity 1 -
Motor Total rated output 0,087 kW
Motor Current 0,40 A
Fan Type Forward multi-vane low noise centrifugal fan -
Fan Quantity 2 -
Sound Pressure Level at 1 m - 44 dB(A)
Connection Pipe Size Water Inlet / Outlet 3 / 4 inch
Connection pipe size Condenset drain 3 / 4 inch
Outline Dimensions w x d x h 1168 x 510 x 245 mm
Package Dimensions w x d x h 1233 x 575 x 278 mm
Net Weight - 19,5 kg
Gross Weight - 24,5 kg
Remote controller Type YB1F2 (standard) -
Wired controller Type WK-010PA-K (optional) -
Package volume - 0,197 m3
Notes

The specification of products is subject to change based further development of the units by the producer and can be changed without prior notice. Refer to rating label. Data are based on following conditions:

  • Unit is designed only for indoor instalation. Temperature in the room should be between 5°C and 43°C, the inlet water should be between 7°C and 60°C
  • Testing conditions for cooling mode: dry bulb temperature DB=27°C, wet bulb temperature WB=19°C, inlet water temperature 7°C and outlet water temperature 12°C
  • Testing conditions for heating mode: dry bulb temperature DB=21°C, inlet water temperature 50°C and outlet water temperature 40°C
  • Testing conditions for freeze-up mode: dry bulb temperature DB=27°C, wet bulb temperature WB=24°C, inlet water temperature 6°C and outlet water temperature 10°C
  • Noise measured 1m below air outlet at 1m distance

Power input is tested under standard condition.

Our Clients And Business Partners

Our strength is quality products with reasonable price setting. We have very wide product range, with very good stock availability whole year round. We put emphasis on aftersales service, spare parts availability and technical support, also we provide technical trainings. With our partners we create long term, mutually benefitial business cooperation.

Your choices regarding the setting of cookies on this website: Read our cookie policy