MINI CHILLERS

SCV-120EA

  • Energy saving - energy class A+
  • High efficient DC inverter compressor and DC fan motor
  • Low noise emission
  • Integrated and compact design - include hydraulic module
  • Reliable operation - built-in controller and water pressure gauge
Power supply - 380-415/3/50 V/Ph/Hz
Cooling 1 Capacity 11,2 (3,1-12,0) kW
Cooling 1 Rated input 3380 W
Cooling 1 Rated current 5,5 A
Cooling 1 EER 3,31 -
Cooling 2 Capacity 12,2 kW
Cooling 2 Rated input 2600 W
Cooling 2 EER 4,70 -
Cooling 2 SEER 6,18 -
Heating 1 Capacity 12,3 (3,3-13,2) kW
Heating 1 Rated input 3720 W
Heating 1 Rated current 6,1 A
Heating 1 COP 3,31 -
Heating 2 Capacity 13,0 kW
Heating 2 Rated input 2850 W
Heating 2 COP 4,56 -
Heating 2 SCOP 3,66 -
Seasonal space heating energy efficiency - 143,5% -
Seasonal space heating energy efficiency class - A+ -
Max. input current - 8,9 A
Compressor Type rotary -
Outdoor fan Motor type DC Motor -
Outdoor fan Air flow 7000 m3/h
Air heat exchanger Type Fin-coil -
Water heat exchanger Type Plate heat exchanger -
Water heat exchanger Water volume 0,78 l
Water heat exchanger Water flow 2,15 m3/h
Water heat exchanger Water pressure drop 18 kPa
Water pump Pump head 8,5 m
Water pump Max. Water Volume 4 m3 / h
Expansion tank volume - 3 l
Refrigerant Type R410A -
Refrigerant Charge volume 2,8 / 5,8 kg / t eq. CO2
Refrigerant Throttle type EXV -
Sound power level - 70 dB(A)
Sound Pressure Level at 1 m - 62 dB(A)
Unit net dimension (wxhxd) 970x1327x400 mm
Packing dimension (wxhxd) 1082x1456x435 mm
Net / Gross weight - 111 / 122 kg
Max. and Min. water inlet pressure - 500 / 150 kPa
Pipe connections Water inlet/outlet 1-1/4 inch
Controller - Electronic -
Ambient temperature range Cooling -5~46 °C
Ambient temperature range Heating -15~27 °C
Water inlet temperature range Cooling 10 ~ 20 °C
Water inlet temperature range Heating 35 ~ 50 °C
Package volume - 0,685 m3
Notes

The specification of products is subject to change based further development of the units by the producer and can be changed without prior notice. Refer to rating label. Data are based on following conditions:

  • Cooling 1: Condenser air in 35°C. Evaporator water in/out 12/7°C.
  • Cooling 2: Condenser air in 35°C. Evaporator water in/out 23/18°C.
  • Heating 1: Condenser air in 7°C, 85% R.H. Evaporator water in/out 40/45°C.
  • Heating 2: Condenser air in 7°C, 85% R.H. Evaporator water in/out 30/35°C.
  • Sound power level: 1m far from fan side of unit in open field.
  • The Max. and Min. water inlet pressure: The maximum and minimum operating pressure values refer to the activation of the pressure switches.

The above data test reference standard EN14511:2013; EN14825:2013; EN50564:2011; EN12102:2011; (EU)No:811:2013; (EU)No:813:2013; OJ 2014/C 207/02:2014.

  • Refrigerant: R410A (50% HFC-32, 50% HFC-125) with GWP (Global Warming Potential) 2088
  • Hermetically sealed equipment

The devices contains fluorinated greenhouse gases covered by the Kyoto Protocol. Noise is tested in the semi-anechoic room, so it should be slightly higher in the actual Operation due to environmental change. Power input is tested under standard condition.

Our Clients And Business Partners

Our strength is quality products with reasonable price setting. We have very wide product range, with very good stock availability whole year round. We put emphasis on aftersales service, spare parts availability and technical support, also we provide technical trainings. With our partners we create long term, mutually benefitial business cooperation.

Your choices regarding the setting of cookies on this website: Read our cookie policy