OUTDOOR UNITS – MODULAR

SDV5-450EAM

  • Cooling capacity 45,0 kW
  • Heating capacity 45,0 kW
  • Indoor units are separate products
Horse Power HP 16 -
Power Supply - 380–415 / 3 / 50 V / Ph / Hz
Capacity Cooling 45,0 kW
Power Input Cooling 12,0 kW
EER - 3,80 kW / kW
Capacity Heating 45,0 kW
Power Input Heating 9,8 kW
COP - 4,60 kW / kW
Combination of Indoor Units - 50–130 % of Outdoor Unit Capacity -
Number of indoor units - 26 pcs
Refrigerant / Charge / Eq. CO2 - R410A / 13,0 / 27,1 type / kg / t
Compressor Type DC Inverter EVI -
Compressor Quantity 1 -
Compressor Oil FV68H -
Operating Range - Cooling - - 5 ~ 48 °C
Operating Range - Heating - - 25 ~ 24 °C
Sound Pressure Level at 1 m - 65 dB(A)
Sound power level - 88 dB(A)
Airflow - 13000 m3 / h
Net Weight - 277,0 kg
Gross Weight - 304,0 kg
Net Dimension w x h x d 1340 x 1635 x 850 mm
Packing Dimensions w x h x d 1405 x 1805 x 910 mm
Package volume - 2,308 m3
Pipe Diameter Liquid Side 15,9 mm
Pipe Diameter Gas Side 31,8 mm
Notes

The specification of products is subject to change based on further development of units by the producer and can be changed without prior notice. Refer to rating label.
R410A (50% HFC-32, 50% HFC-125), GWP of refrigerant used: 2088.
Contains fluorinated greehouse gases covered by the Kyoto Protocol.

Modular units may be connected to one refrigerant circuit, max 3 pcs up to 270 kW.

Our Clients And Business Partners

Our strength is quality products with reasonable price setting. We have very wide product range, with very good stock availability whole year round. We put emphasis on aftersales service, spare parts availability and technical support, also we provide technical trainings. With our partners we create long term, mutually benefitial business cooperation.