CASSETTE UNITS

SF-16C

  • Indoor unit
  • Cooling capacity 8,7kW
  • Heating capacity 12,9kW
  • Elegant look
  • Low noise
  • Remote control
  • Optional wired controller Z4E351B
  • Outdoor unit is separate product
Power System Type 220 - 240 / 1 / 50 V / Ph / Hz
Power System Input 160,0 W
Air Flow Volume High 965 m3 / h
Air Flow Volume High 1640 ft3 / min
Air Flow Volume Medium 853 m3 / h
Air Flow Volume Medium 1450 ft3 / min
Air Flow Volume Low 781 m3 / h
Air Flow Volume Low 1328 ft3 / min
Capacity Cooling 8700 W
Capacity Heating 12900 W
Electric Heater Rated Power - 1400 W
Water System Water Flow Volume 1,53 m3 / h
Water System Pressure Drop 27 kPa
Sound Pressure Level La at 1 m - 53 dB
Coil Type Aluminium Fin - Copper Tube -
Coil Operating Pressure less than 1,6 MPa
Electric Motor Type FN50T
Electric Motor Capacitor 4,5 uF
Connection Pipe Size Water Inlet / Outlet 3 / 4 inch
Connection Pipe Size Condensate Drain 32 mm
Outline Dimensions Body 840 x 840 x 320 mm
Outline Dimensions Panel 960 x 960 x 60 mm
Package Dimensions Body 960 x 960 x 394 mm
Package Dimensions Panel 1040 x 1025 x 115 mm
Net Weight Body 38,0 kg
Net Weight Panel 6,5 kg
Gross Weight Body 46,0 kg
Gross Weight Panel 10 kg
Remote controller Type YB1F2 (standard) -
Wired controller Type Z4E351B (optional) -
Package volume Body 0,363 m3
Package volume Panel 0,123 m3
Notes

The specification of products is subject to change based further development of the units by the producer and can be changed without prior notice. Refer to rating label. Data are based on following conditions:

  • Unit is designed only for indoor instalation. Temperature in the room should be between 5°C and 43°C, the inlet water should be between 7°C and 60°C
  • Testing conditions for cooling mode: dry bulb temperature DB=27°C, wet bulb temperature WB=19°C, inlet water temperature 7°C and outlet water temperature 12°C
  • Testing conditions for heating mode: dry bulb temperature DB=21°C, inlet water temperature 50°C and outlet water temperature 40°C
  • Testing conditions for freeze-up mode: dry bulb temperature DB=27°C, wet bulb temperature WB=24°C, inlet water temperature 6°C and outlet water temperature 10°C
  • Noise measured 1m below air outlet at 1m distance

Power input is tested under standard condition.

Our Clients And Business Partners

Our strength is quality products with reasonable price setting. We have very wide product range, with very good stock availability whole year round. We put emphasis on aftersales service, spare parts availability and technical support, also we provide technical trainings. With our partners we create long term, mutually benefitial business cooperation.

Your choices regarding the setting of cookies on this website: Read our cookie policy