MINI CHILLERS

SCV-120EB

  • Energy-efficient – energy class A+++
  • High-performance DC inverter compressor and DC fan motor
  • Low noise
  • Integrated and compact design – including hydraulic module
  • Reliable operation
  • SWC-120F controller included
  • WiFi application, MODBUS support
Power supply - 220-240/1/50 V/Ph/Hz
Heating A7W35 Capacity 12200 W
Heating A7W35 Rated Input 2490 W
Heating A7W35 COP 4,90 -
Heating A2W35 Capacity 12300 W
Heating A2W35 Rated Input 3417 W
Heating A2W35 COP 3,60 -
Cooling A35W7 Capacity 11600 W
Cooling A35W7 Rated Input 3742 W
Cooling A35W7 EER 3,10 -
Cooling A35W18 Capacity 12200 W
Cooling A35W18 Rated Input 2652 W
Cooling A35W18 EER 4,6 -
Seasonal Space Heating Energy Efficiency Class Water Outlet at 35 °C A+++ -
SCOP Average Climate Water Outlet at 35 °C 5,08 -
SCOP Average Climate Water Outlet at 55 °C 3,62 -
SEER Water Outlet at 7 °C 5,08 -
SEER Water Outlet at 18 °C 7,79 -
Sound Power Level Cooling Max. 74 dB(A)
Sound Power Level Heating Max. 74 dB(A)
Sound Pressure Level at 1 m - 56 dB(A)
Compressor Type DC Twin Rotary -
Outdoor fan Motor type DC Motor -
Outdoor fan Air flow 7000 m3/h
Air heat exchanger Type Fin-coil -
Water heat exchanger Type Plate heat exchanger -
Rated Water Flow - 2,10 m3 / h
Water Flow Range - 0,70 ~ 2,50 m3 / h
Water Pump Type DC -
Water Pump Max. Pump Head 9 m
Expansion tank volume - 5 l
Safety Valve - 0,3 MPa
Flow Switch - 0,3 m3 / h
Throttle Type Electromagnetic Expansion Valve -
Refrigerant Type R32 -
Refrigerant Charge volume 1,8 / 1,22 kg / t eq. CO2
Unit net dimension (wxhxd) 1040 × 865 × 410 mm
Packing dimension (wxhxd) 1190 × 970 × 560 mm
Net / Gross weight - 106 / 122 kg
Pipe Connections Water Inlet / Outlet G5/4"BSP -
Controller - Wired Controller SWC-120F (Standard) -
Ambient temperature range Cooling -5~43 °C
Ambient temperature range Heating -25~35 °C
Water outlet temperature range Cooling 5~25 °C
Water outlet temperature range Heating 25~65 °C
Notes

1. The above data is based on EN14511; EN14825; EN50564; EN12102; (EU)No:811/2013; (EU)No:813/2013; OJ 2014/C 207/02.

2. The sound pressure level is measured 1 m in front of the unit and at a height of (1+H) / 2 m (where H is the height of the unit) above the ground in a partially soundproof room. During operation at the installation site, the sound pressure level may be higher due to ambient noise.

The technical specification of the products may differ from the stated values according to product development by the manufacturer. Please refer to the parameters on the unit nameplate. This equipment contains fluorinated greenhouse gases covered by the Kyoto Protocol. R32 (100% HFC-32) with GWP (Global Warming Potential): 675.

Our Clients And Business Partners

Our strength is quality products with reasonable price setting. We have very wide product range, with very good stock availability whole year round. We put emphasis on aftersales service, spare parts availability and technical support, also we provide technical trainings. With our partners we create long term, mutually benefitial business cooperation.