SCV-160EB-3
- Energy-efficient – energy class A+++
- High-performance DC inverter compressor and DC fan motor
- Low noise
- Integrated and compact design – including hydraulic module
- Reliable operation
- SWC-120F controller included
- WiFi application, MODBUS support
Power supply | - | 380-415/3/50 | V/Ph/Hz |
Heating A7W35 | Capacity | 16000 | W |
Heating A7W35 | Rated Input | 3556 | W |
Heating A7W35 | COP | 4,50 | - |
Heating A2W35 | Capacity | 14500 | W |
Heating A2W35 | Rated Input | 4462 | W |
Heating A2W35 | COP | 3,25 | - |
Cooling A35W7 | Capacity | 14000 | W |
Cooling A35W7 | Rated Input | 4828 | W |
Cooling A35W7 | EER | 2,90 | - |
Cooling A35W18 | Capacity | 15400 | W |
Cooling A35W18 | Rated Input | 3667 | W |
Cooling A35W18 | EER | 4,2 | - |
Seasonal Space Heating Energy Efficiency Class | Water Outlet at 35 °C | A+++ | - |
SCOP Average Climate | Water Outlet at 35 °C | 4,84 | - |
SCOP Average Climate | Water Outlet at 55 °C | 3,59 | - |
SEER | Water Outlet at 7 °C | 4,84 | - |
SEER | Water Outlet at 18 °C | 7,54 | - |
Sound Power Level | Cooling Max. | 74 | dB(A) |
Sound Power Level | Heating Max. | 74 | dB(A) |
Sound Pressure Level at 1 m | - | 59 | dB(A) |
Compressor | Type | DC Twin Rotary | - |
Outdoor fan | Motor type | DC Motor | - |
Outdoor fan | Air flow | 7000 | m3/h |
Air heat exchanger | Type | Fin-coil | - |
Water heat exchanger | Type | Plate heat exchanger | - |
Rated Water Flow | - | 2,75 | m3 / h |
Water Flow Range | - | 0,70 ~ 3,00 | m3 / h |
Water Pump | Type | DC | - |
Water Pump | Max. Pump Head | 9 | m |
Expansion tank volume | - | 5 | l |
Safety Valve | - | 0,3 | MPa |
Flow Switch | - | 0,3 | m3 / h |
Throttle | Type | Electromagnetic Expansion Valve | - |
Refrigerant | Type | R32 | - |
Refrigerant | Charge volume | 1,8 / 1,22 | kg / t eq. CO2 |
Unit net dimension | (wxhxd) | 1040 × 865 × 410 | mm |
Packing dimension | (wxhxd) | 1190 × 970 × 560 | mm |
Net / Gross weight | - | 120 / 136 | kg |
Pipe Connections | Water Inlet / Outlet | G5/4"BSP | - |
Controller | - | Wired Controller SWC-120F (Standard) | - |
Ambient temperature range | Cooling | -5~43 | °C |
Ambient temperature range | Heating | -25~35 | °C |
Water outlet temperature range | Cooling | 5~25 | °C |
Water outlet temperature range | Heating | 25~65 | °C |
Notes |
1. The above data is based on EN14511; EN14825; EN50564; EN12102; (EU)No:811/2013; (EU)No:813/2013; OJ 2014/C 207/02. 2. The sound pressure level is measured 1 m in front of the unit and at a height of (1+H) / 2 m (where H is the height of the unit) above the ground in a partially soundproof room. During operation at the installation site, the sound pressure level may be higher due to ambient noise. The technical specification of the products may differ from the stated values according to product development by the manufacturer. Please refer to the parameters on the unit nameplate. This equipment contains fluorinated greenhouse gases covered by the Kyoto Protocol. R32 (100% HFC-32) with GWP (Global Warming Potential): 675. |