SCV-300EBH
- Optional modular interconnection
- Option to interconnect up to 16 modules
- All interconnected units can be controlled by a single wired controller
- PCB allows to remotely control of the following functions: ON / OFF, heating / cooling, alarm
- High-efficient DC inverter compressor
- The wall-mounted controller KJRM-120H included in the package
- MODBUS support
Power supply | - | 380-415/3/50 | V/Ph/Hz |
Cooling 1 | Capacity | 27,5 | kW |
Cooling 1 | Input | 11,0 | kW |
Cooling 1 | EER | 2,50 | - |
Cooling 1 | SEER | 4,25 | - |
Heating 1 | Capacity | 32 | kW |
Heating 1 | Input | 10,7 | kW |
Heating 1 | COP | 2,99 | - |
Heating 1 | SCOP | 3,99 | - |
Max. running current | - | 21,5 | A |
Compressor | Type | DC invertor rotary | - |
Compressor | Quantity | 1 | - |
Air side heat exchanger | Type | Finned tube | - |
Air side heat exchanger | Quantity of fan motor | 1 | - |
Air side heat exchanger | Air flow | 12500 | m3/h |
Water side heat exchanger | Type | Plate | - |
Water side heat exchanger | Water pressure drop | 130 | kPa |
Water side heat exchanger | Volume | 2,44 | l |
Water side heat exchanger | Water flow volume | 5,0 | m3/h |
Refrigerant | Type | R32 | - |
Refrigerant | Charge volume | 7,9 / 5,3 | kg / t eq. CO2 |
Refrigerant | Throttle type | EXV | - |
Sound Pressure Level at 1 m | - | 65 | dB(A) |
Unit net dimension | (wxhxd) | 1870 x 1175 x 1000 | mm |
Packing dimension | (wxhxd) | 1910 x 1225 x 1035 | mm |
Net / Gross weight | - | 315 / 325 | kg |
Pipe Connections | Water Inlet / Outlet | DN40 | mm |
Water Pipe | Connection Type | Threaded Connection | - |
Controller | - | Wired Controller KJRM-120H (Standard) | - |
Ambient temperature range | Cooling | -10~43 | °C |
Ambient temperature range | Heating | -14~30 | °C |
Water outlet temperature range | Cooling | 5~20 | °C |
Water outlet temperature range | Heating | 25~54 | °C |
Notes |
The rated capacity is based on the following conditions:
The technical specification of the products may differ from the stated values according to product development by the manufacturer. Please refer to the parameters on the unit nameplate. This equipment contains fluorinated greenhouse gases covered by the Kyoto Protocol. The noise level is tested in an anechoic chamber, the actual values may be affected by local conditions. The input power values under standard conditions. R32 (100% HFC-32) with GWP: 675. |