MODULAR COMMERCIAL HEAT PUMPS / CHILLERS

SCV-900EB

  • Optional modular interconnection
  • Option to interconnect up to 16 modules
  • All interconnected units can be controlled by a single wired controller
  • PCB allows to remotely control of the following functions: ON / OFF, heating / cooling, alarm
  • High-efficient DC inverter compressor
  • Cost-effective operation
  • Flexible connection of pipes and installation
  • The wall-mounted controller KJRM-120H2 included in the package
Power supply - 380-415/3/50 V/Ph/Hz
Cooling 1 Capacity 82 kW
Cooling 1 Input 27,8 kW
Cooling 1 EER 2,95 -
Cooling 1 SEER 4,50 -
Heating 1 Capacity 90 kW
Heating 1 Input 28,1 kW
Heating 1 COP 3,20 -
Heating 1 SCOP 3,97 -
Max. running current - 43,3 A
Compressor Type DC invertor rotary -
Compressor Quantity 2 -
Air side heat exchanger Type Finned tube -
Air side heat exchanger Quantity of fan motor 2 -
Air side heat exchanger Air flow 35000 m3/h
Water side heat exchanger Type Plate -
Water side heat exchanger Water pressure drop 75 kPa
Water side heat exchanger Volume 7,05 l
Water side heat exchanger Water flow volume 15,0 m3/h
Refrigerant Type R32 -
Refrigerant Charge volume 16** (11,5 + 4,5) / 10,8 kg / t eq. CO2
Refrigerant Throttle type EXV -
Sound Pressure Level at 1 m - 65 dB(A)
Unit net dimension (wxhxd) 2220 × 2315 × 1135 mm
Packing dimension (wxhxd) 2250 × 2445 × 1180 mm
Net / Gross weight - 635 / 660 kg
Pipe Connections Water Inlet / Outlet DN50 mm
Water Pipe Connection Type Clasp Connection -
Controller - Wired Controller KJRM-120H (Standard) -
Ambient temperature range Cooling -10~48 °C
Ambient temperature range Heating -20~43 °C
Water outlet temperature range Cooling 5~20 °C
Water outlet temperature range Heating 25~54 °C
Notes

Nominal capacity is based on the following conditions:

  • Cooling: Chilled water inlet / outlet temperature: 12 / 7 °C, outdoor ambient temperature 35 °C DB.
  • Heating: Warm water inlet / outlet temperature: 40 / 45 °C, outdoor ambient temperature 7 °C DB / 6 °C WB.
  • Sound pressure level is measured at a position 1 m in front of the unit and 1,1 m above the floor in a semi-anechoic chamber.
  • Water side fouling factor: 0,086 m2 ˚C / kW.

* The  total  amount  of  refrigerant  is 16 kg, including the 11,5 kg already charged before delivery and the 4,5 kg to be charged.
** The  total  amount  of  refrigerant  is 15,5 kg, including the 11,5 kg already charged before delivery and the 4 kg to be charged.
*** The  total  amount  of  refrigerant  is 32 kg, including the 2 × 5,5 kg already charged before delivery and the 2 × 10,5 kg to be charged.

The specification of products is subject to change based on further development of the units by the producer and can be changed without prior notice. Refer to rating label.
Contains fluorinated greenhouse gases covered by the Kyoto Protocol.
Noise is tested in the semi-anechoic room, so it should be slightly higher due to change of location. Power input is tested under standard conditions.
R32 (100% HFC-32), GWP of refrigerant: 675.

Our Clients And Business Partners

Our strength is quality products with reasonable price setting. We have very wide product range, with very good stock availability whole year round. We put emphasis on aftersales service, spare parts availability and technical support, also we provide technical trainings. With our partners we create long term, mutually benefitial business cooperation.

Your choices regarding the setting of cookies on this website: Read our cookie policy