SDV6-DM90
- DC fan motor
- Cooling capacity 9,0 kW
- Heating capacity 10,0 kW
- 7 speed of fan (28–39 dB)
- External static pressure up to 160 Pa
- Outdoor unit is separate product
Capacity | Cooling | 9,0 | kW |
Capacity | Heating | 10,0 | kW |
Power Supply | - | 220–240 / 1 / 50 | V / Ph / Hz |
Power Input | - | 110 | W |
Air Flow | Indoor Unit | 1420 / 1323 / 1225 / 1128 / 1030 / 933 / 835 | m3 / h |
Sound Pressure Level at 1,4 m | - | 37 / 36 / 34 / 33 / 31 / 30 / 28 | dB(A) |
Sound power level | - | 59 / 57 / 55 / 53 / 51 / 48 / 46 | dB(A) |
External Static Pressure | Nom. (Min–Max) | 40 (10-160) | Pa |
Net Dimension | w x h x d | 1160 x 245 x 770 | mm |
Packing Dimensions | w x h x d | 1215 x 305 x 890 | mm |
Net Weight | - | 31,0 | kg |
Gross Weight | - | 34,5 | kg |
Throttle | Type | Electromagnetic Expansion Valve | - |
Refrigerant | Type | R410A or R32 | - |
Pipe Diameter | Liquid Side | 9,5 | mm |
Pipe Diameter | Gas Side | 15,9 | mm |
Pipe Diameter | Drainage Pipe | 25 | mm |
Set Temperature range | - | 17 ~ 30 | °C |
Notes | The specification of products is subject to change based on further development of units by the producer and can be changed without prior notice. Refer to rating label. |
OPTIONAL ACCESSORIES
KNX-03 BMS GATEWAY
SCC-61 CENTRAL CONTROLLER
SDV6-BAC BMS GATEWAY
SDV6-MOD BMS GATEWAY
SRC-61 REMOTE CONTROLLER
SWC-61 WIRED CONTROLLER
SWC-62 GROUP CONTROLLER