SDV6-E785ATI
- Cooling capacity 78,5 kW
- Heating capacity 78,5 kW
- Indoor units are separate products
- Heat up to -30 °C outside temperature
- DC inverter compressor
- Autoaddressing of indoor units
- Convenient installation
- Wide operational temperature range
- Space saving design
- Improved noise reduction design
- Low noise DC fan motor
- Dry contacts (forced stop, alarm, defrost)
Horse Power | HP | 28 | - |
Power Supply | - | 380–415 / 3 / 50 | V / Ph / Hz |
Capacity | Cooling | 78,5 | kW |
Power Input | Cooling | 32,4 | kW |
EER | - | 2,42 | kW / kW |
Capacity | Heating | 78,5 | kW |
Power Input | Heating | 24,5 | kW |
COP | - | 3,20 | kW / kW |
SEER | - | 5,93 | - |
ηs,c | - | 234,2 | % |
SCOP | SCOP | 4,1 | |
ηs,h | - | 161,8 | % |
Combination of Indoor Units | - | 50–130 % of Outdoor Unit Capacity | - |
Number of indoor units | - | 46 | pcs |
Compressor | Type | DC Inverter EVI | - |
Compressor | Quantity | 2 | - |
Compressor | Oil | FVC68D | - |
Operating Range - Cooling | - | - 15 ~ 55 | °C |
Operating Range - Heating | - | - 30 ~ 30 | °C |
Sound Pressure Level at 1 m | - | 68 | dB(A) |
Sound power level | - | 93 | dB(A) |
Airflow | - | 28000 | m3 / h |
Net Weight | - | 396,0 | kg |
Gross Weight | - | 426,0 | kg |
Net Dimension | w x h x d | 1880 x 1760 x 825 | mm |
Packing Dimensions | w x h x d | 1945 x 1945 x 890 | mm |
Refrigerant / Charge / Eq. CO2 | - | R410A / 11,96 / 24,97 | type / kg / t |
Vertical Pipe Length | On Top / Bellow | 110 | m |
Pipe Length from 1. Branch | - | 40 | m |
Equivalent Pipe Length | - | 260 | m |
Total Pipe Length | - | 1100 | m |
Pipe Diameter | Liquid Side | 22,2 | mm |
Pipe Diameter | Gas Side | 34,9 | mm |
Notes | The specification of products is subject to change based on further development of units by the producer and can be changed without prior notice. Refer to rating label. |
OPTIONAL ACCESSORIES
SDV6-CLOUD CENTRAL CONTROLLER
SDV5-MOD BMS GATEWAY
SDV5-BAC BMS GATEWAY
SDV6-MOD BMS GATEWAY
SDV6-BAC BMS GATEWAY
SDV6-EK EXTENSION KIT