SDV6-E120BS-3
- Ecological refrigerant R32
- DC inverter compressor
- Autoaddressing of indoor units
- Convenient installation
- Wide operational temperature range
- Space saving design, small footprint
- Improved noise reduction design
- Low noise DC fan motor
- Dry contacts (forced stop, alarm, defrost)
- Option safety stop valve SDV6-RSD
Horse Power | HP | 4,4 | - |
Power Supply | - | 220–240 / 1 / 50 | V / Ph / Hz |
Capacity | Cooling | 12,3 | kW |
Power Input | Cooling | 3,37 | kW |
EER | - | 3,65 | kW / kW |
SEER | - | 7,80 | - |
ηs,c | - | 309,0 | % |
Capacity | Heating (max.) | 14,0 | kW |
Power Input | Heating (max.) | 3,59 | kW |
COP | - | 3,90 | kW / kW |
SCOP | SCOP | 4,90 | |
ηs,h | - | 193,0 | % |
Combination of Indoor Units | - | 50–160 % of Outdoor Unit Capacity | - |
Number of indoor units | - | 8 | pcs |
Compressor | Type | DC Inverter | - |
Compressor | Quantity | 1 | - |
Compressor | Oil | FVC68D | - |
Operating Range - Cooling | - | - 15 ~ 52 | °C |
Operating Range - Heating | - | - 20 ~ 16,5 (WB) | °C |
Sound Pressure Level at 1 m | - | 55 | dB(A) |
Sound power level | - | 72 | dB(A) |
Airflow | - | - | m3 / h |
Net Weight | - | 110,0 | kg |
Gross Weight | - | 121,0 | kg |
Net Dimension | w x h x d | 1038 x 864 x 409 | mm |
Packing Dimensions | w x h x d | 1120 × 980 × 560 | mm |
Refrigerant / Charge / Eq. CO2 | - | R32 / 2,85 / 1,59 | type / kg / t |
Vertical Pipe Length | On Top / Bellow | 50 / 40 | m |
Pipe Length from 1. Branch | - | 40 | m |
Equivalent Pipe Length | - | 120 | m |
Total Pipe Length | - | 300 | m |
Pipe Diameter | Liquid Side | 9,5 | mm |
Pipe Diameter | Gas Side | 15,9 | mm |
Notes | The specification of products is subject to change based on further development of units by the producer and can be changed without prior notice. Refer to rating label. |
OPTIONAL ACCESSORIES
SDV6-CLOUD CENTRAL CONTROLLER
SDV5-MOD BMS GATEWAY
SDV5-BAC BMS GATEWAY
SDV6-MOD BMS GATEWAY
SDV6-BAC BMS GATEWAY
SDV6-EK EXTENSION KIT