SMH-160IRB2
- The system can be connected to underfloor heating, radiators, and fan coils. If you add a hot water tank and a three-way valve, you can also use the system to heat domestic hot water (DHW)
- Ideal solution if you do not have the option of installing an indoor unit indoors
- All you have to do is connect the device to the heating system and the mains. This minimises costs and installation time
- Environmentally friendly R32 refrigerant in combination with an inverter compressor and EVI heat exchanger ensures economical and nature-saving operation
- Hermetically sealed refrigerant circuit, minimal risk of refrigerant leakage
- Monoblock heat pump includes a circulation pump, plate heat exchanger, air valve, expansion valve, safety valve and two-stage rotary compressor
- The unit operates reliably even at low temperatures, down to -25 °C, thanks to the added economizer and intermediate refrigerant injection
- The leaving water temperature is 20 to 60 °C
- Keymark Certification
Capacity 1 | Heating Floor Heating | 15,5 | kW |
Capacity 1 | Cooling Floor Cooling | 14,5 | kW |
Power Input 1 | Heating Floor Heating | 3,60 | kW |
Power Input 1 | Cooling Floor Cooling | 3,82 | kW |
COP 1 | Heating Floor Heating | 4,30 | - |
EER 1 | Cooling Floor Cooling | 3,7 | - |
Capacity 2 | Heating Fan Coil or Radiator | 15,5 | kW |
Capacity 2 | Cooling for Fan Coil | 13,0 | kW |
Power Input 2 | Heating Fan Coil or Radiator | 4,7 | kW |
Power Input 2 | Cooling for Fan Coil | 4,73 | kW |
COP 2 | Heating Fan Coil or Radiator | 3,4 | - |
EER 2 | Cooling for Fan Coil | 2,70 | - |
Energy class | - | A++ | - |
SCOP | Heating (55 °C / 35 °C) | 3,20 / 4,20 | - |
Power Supply | - | 220 - 240 / 1 / 50 | V / Ph / Hz |
Rated Power Input | - | 17,0 | kW |
Rated Current | - | 34,00 | A |
Refrigerant / Charge / Eq. CO2 | - | R32 / 2,20 / 1,49 | type / kg / t |
Water pipes | Inlet | DN25 | mm |
Water pipes | Outlet | DN25 | mm |
Water temperature range | Heating | 20 ~ 60 | °C |
Water temperature range | Cooling | 7 ~ 25 | °C |
Water Pump | Max. Flow | 3,5 | m3 / h |
Water pump | Power input | 75 | W |
Water Flow Switch | Minimum Flow | 0,6 | m3 / h |
Expansion tank | Volume | 2 | l |
Expansion tank | Maximum pressure | 3 | Bar |
Expansion tank | Precharged pressure | 1 | Bar |
Electric heater | Mode | - | |
Electric Heater | Steps | - | - |
Electric Heater | Capacity | - | kW |
Electric Heater | Combination | - | - |
Electric heater | Voltage / phase / frequency | - | V / f / Hz |
Heat Exchanger | Type | Brazed Plate HEX | - |
Heat Exchanger | Quantity | 1 | - |
Safety Valve | - | 3 | Bar |
Sound Pressure Level Lpa at 1 m | Heating | 61 | dB |
Sound Pressure Level Lpa at 1 m | Cooling | 59 | dB |
Dimension | (w x h x d) | 1200 × 878 × 460 | mm |
Package dimension | (w x h x d) | 1288 × 1020 × 588 | mm |
Net Weight | - | 151 | kg |
Gross Weight | - | 166 | kg |
Operating Temperature Range | Cooling | 10 ~ 48 | °C |
Operating Temperature Range | Heating | - 25 ~ 35 | °C |
Operating Temperature Range | Water heating | - 25 ~ 45 | °C |
Notes |
The specification of products is subject to change based further development of the units by the producer and can be changed without prior notice. Refer to rating label. 1. Capacities and power inputs are based on the following conditions:
2. Capacities and power inputs are based on the following conditions:
|