SMHM-650B-3
- Modular interconnection possible
- Up to 16 modules can be connected
- All interconnected units can be controlled by one wired controller
- On the PCB it is possible to remotely control: ON / OFF, heating / cooling, alarm
- High efficiency DC inverter compressor
- Economical operation
- Flexible piping and installation
- KJRM-120H2 wall-mounted controller included
- Maximum temperature up to 65 °C
- Higher efficiency
- Modular connection of up to 16 units
- Heat Pumps
- Chillers
- MODULAR COMMERCIAL HEAT PUMPS / CHILLERS
- S-THERM YUKON COMMERCIAL MONOBLOCK HEAT PUMPS
Power supply | - | 380-415/3/50 | V/Ph/Hz |
Cooling A35W7 | Capacity | 57000 | W |
Cooling A35W7 | Rated Input | 19000 | W |
Cooling A35W7 | EER | 3,00 | - |
Cooling A35W7 | SEER | 5,00 | - |
Heating A7W45 | Capacity | 65,00 | kW |
Heating A7W45 | Input | 18,30 | kW |
Heating A7W45 | COP | 3,55 | - |
Heating A7W35 | Capacity | 64000 | W |
Heating A7W35 | Rated Input | 15240 | W |
Heating A7W35 | COP | 4,20 | - |
Heating A7W35 | SCOP (W35 average) | 4,50 | - |
Compressor | Type | DC invertor rotary | - |
Compressor | Quantity | 1 | - |
Air side heat exchanger | Type | Finned tube | - |
Air side heat exchanger | Quantity of fan motor | 2 | - |
Air side heat exchanger | Air flow | 22000 | m3/h |
Water side heat exchanger | Type | Plate | - |
Water side heat exchanger | Water pressure drop | 44 | kPa |
Water side heat exchanger | Volume | 5,17 | l |
Water side heat exchanger | Water flow volume | 3~14 | m3/h |
Refrigerant | Type | R32 | - |
Refrigerant | Charge volume | 9 / 6,075 | kg / t eq. CO2 |
Refrigerant | Throttle type | EXV | - |
Sound power level A7W45 | - | 80 | dB(A) |
Sound pressure level at 1 m A7W45 | - | 64 | dB(A) |
Silent mode sound power level A7W45 | - | 77 | dB(A) |
Super silent mode sound power level A7W45 | - | 74 | dB(A) |
Unit net dimension | (wxhxd) | 2000 x 1770 x 960 | mm |
Packing dimension | (wxhxd) | 2085 x 1890 x 1030 | mm |
Net / Gross weight | - | 440 / 455 | kg |
Pipe Connections | Water Inlet / Outlet | DN50 | mm |
Water Pipe | Connection Type | Hoop connection | - |
Controller | - | Wired Controller KJRM-120H2 (Standard) | - |
Ambient temperature range | Cooling | -15~48 | °C |
Ambient temperature range | Heating | -25~43 | °C |
Ambient temperature range | DHW | -20~43 | ℃ |
Water outlet temperature range | Cooling | 5~20 | °C |
Water outlet temperature range | Heating | 25~65 | °C |
Water outlet temperature range | DHW - heat pump | 30~62 | ℃ |
Water outlet temperature range | DHW | 30~70 | ℃ |
Notes |
Water-side clogging factor: 0.086 m2 °C/kW. The total quantity of refrigerant is 15.5 kg, including 11.5 kg already filled before delivery and 4 kg to be replenished. The specifcation of products is subject to change based on further development of the units by the producer and can be changed without prior notice. Refer to rating label. |