S-THERM YUKON COMMERCIAL MONOBLOCK HEAT PUMPS

SMHM-1400BH-3

  • Modular interconnection possible
  • Up to 16 modules can be connected
  • All interconnected units can be controlled by one wired controller
  • On the PCB it is possible to remotely control: ON / OFF, heating / cooling, alarm
  • High efficiency DC inverter compressor
  • Economical operation
  • Flexible piping and installation
  • KJRM-120H2 wall-mounted controller included
  • Maximum temperature up to 65 °C
  • Higher efficiency
  • Modular connection of up to 16 units
  • Hydraulic module
Cooling A35W7 Capacity 129290 W
Cooling A35W7 Rated Input 52100 W
Cooling A35W7 EER 2,49 -
Cooling A35W7 SEER 4,77 -
Heating A7W45 Capacity 140,94 kW
Heating A7W45 Input 47,10 kW
Heating A7W45 COP 2,99 -
Heating A7W35 Capacity 142940 W
Heating A7W35 Rated Input 40540 W
Heating A7W35 COP 3,53 -
Heating A7W35 SCOP (W35 average) 4,23 -
Compressor Type DC invertor rotary -
Compressor Quantity 2 -
Air side heat exchanger Type Finned tube -
Air side heat exchanger Quantity of fan motor 2 -
Air side heat exchanger Air flow 50000 m3/h
Water side heat exchanger Type Plate -
Water side heat exchanger Volume 11,1 l
Water side heat exchanger Water flow volume 5~26 m3/h
Refrigerant Type R32 -
Refrigerant Charge volume 15,5* (11,5+4) / 10,463 kg / t eq. CO2
Refrigerant Throttle type EXV -
Sound power level A7W45 - 92 dB(A)
Sound pressure level at 1 m A7W45 - 73 dB(A)
Silent mode sound power level A7W45 - 88 dB(A)
Super silent mode sound power level A7W45 - 85 dB(A)
Unit net dimension (wxhxd) 2220 x 2300 x 1135 mm
Packing dimension (wxhxd) 2250 x 2445 x 1180 mm
Net / Gross weight - 746 / 767 kg
Pipe Connections Water Inlet / Outlet DN65 mm
Water Pipe Connection Type Hoop connection -
Controller - Wired Controller KJRM-120H2 (Standard) -
Ambient temperature range Cooling -15~48 °C
Ambient temperature range Heating -25~43 °C
Ambient temperature range DHW -20~43
Water outlet temperature range Cooling 5~20 °C
Water outlet temperature range Heating 25~65 °C
Water outlet temperature range DHW - heat pump 30~62
Water outlet temperature range DHW 30~70
Notes

Water-side clogging factor: 0.086 m2 °C/kW.

The total quantity of refrigerant is 15.5 kg, including 11.5 kg already filled before delivery and 4 kg to be replenished.

The specifcation of products is subject to change based on further development of the units by the producer and can be changed without prior notice. Refer to rating label.
Contains fluorinated greenhouse gases covered by the Kyoto Protocol. R32 (100% HFC-32), GWP of refrigerant used: 675.
Sound pressure level is tested in a soundless chamber, actual values may be affected by local conditions.

Our Clients And Business Partners

Our strength is quality products with reasonable price setting. We have very wide product range, with very good stock availability whole year round. We put emphasis on aftersales service, spare parts availability and technical support, also we provide technical trainings. With our partners we create long term, mutually benefitial business cooperation.