S-THERM YUKON OUTDOOR UNITS

MSH-120EB-3

  • Outdoor units of compact dimensions facilitating problem-free installations and also transportation
  • The device uses environmentally friendly refrigerant R32 with low GWP value
  • Compressor with added economizer and intermediate stage injection of refrigerant, thanks to which high efficiency and energy saving are achieved
  • Motor control technology by semiconductor frequency converter
  • The units are equipped with an inverter control that changes the speed of the compressor. The delivered power of the units is precisely adapted to the heating system
  • Energy savings of up to 40% and temperature fluctuations are avoided
  • Between the outdoor unit and the indoor unit, the pipe length can be up to 30 meters. Elevation up to 20 meters.
  • Keymark Certification
  • The indoor unit (MSH-160IB-3/9; MSH-240TB-3/9) is a separate product
Power Supply - 380 - 415 / 3 / 50 V / Ph / Hz
Capacity Heating 12,1 kW
Capacity Cooling 12,0 kW
Power Input Heating 2,40 kW
Power Input Cooling 3,00 kW
COP Heating 4,95 -
EER Cooling 4,00 -
Sound Pressure Level at 1 m - 50 dB(A)
Energy class Heating (55°C / 35°C) A++ / A+++ -
SCOP Heating (55 °C / 35 °C) 3,45 / 4,81 -
Refrigerant / Charge / Eq. CO2 - R32 / 1,84 / 1,24 type / kg / t
Sanitary Water Temperature - 12 ~ 60 °C
Refrigerant Gas Pipe Diameter 5/8 / 16 inch / mm
Refrigerant Liquid Pipe Diameter 3/8 / 9,5 inch / mm
Dimension (w x h x d) 1118 × 865 × 523 mm
Package dimension (w x h x d) 1190 × 970 × 560 mm
Net Weight - 112 kg
Gross Weight - 125,5 kg
Operating Temperature Range - -25 ~ 43 °C
Standard Pipe Length - 15 m
Max. Pipe Length - 30 m
Max. Elevation - 20 m
Additional Refrigerant - 38 g / m
Notes

We offer you outdoor units in a single-propeller version in capacity of 6, 8, 10, 12, 14, 16 kW in single-phase and three-phase versions (units with suffix -3).

CAPACITIES AND POWER INPUTS ARE BASED ON THE FOLLOWING CONDITIONS:

  • COOLING Conditions: Indoor Water Temperature 23 °C / 18 °C. Outdoor Air Temperature 35 °C DB / 24 °C WB.
  • HEATING Conditions: Indoor Water Temperature 30 °C / 35 °C. Outdoor Air Temperature 7 °C DB / 6 °C WB.

The specifcation of products is subject to change based on further development of the units by the producer and can be changed without prior notice.
Refer to rating label. Contains fluorinated greenhouse gases covered by the Kyoto Protocol. R32 (100% HFC-32), GWP of refrigerant used: 675.
Sound pressure level is tested in a soundless chamber, actual values may be affected by local conditions.

imageimageimage

Our Clients And Business Partners

Our strength is quality products with reasonable price setting. We have very wide product range, with very good stock availability whole year round. We put emphasis on aftersales service, spare parts availability and technical support, also we provide technical trainings. With our partners we create long term, mutually benefitial business cooperation.