ASGE-60BI2-3
- Cooling capacity 16,0 kW
- Heating capacity 17,0 kW
- 3-year warranty
- DC Inverter technology
- Autorestart function
- Anticorrosion treatment of exchangers
- SCMI-01.5 slave unit (control by 0–10 V)
- SCMI-01.5 communication module is separate product
Capacity | Cooling / Heating | 16,0 / 17,0 | kW |
Power Supply | Into Outdoor Unit | 380–415 / 3 / 50/60 | V / Ph / Hz |
Power Input | Cooling / Heating | 5,40 / 5,70 | kW |
Rated Power Input | Cooling / Heating | 6,80 | kW |
Power Current | Cooling / Heating | 9,2 / 9,7 | A |
Rated Power Current | Cooling / Heating | 12,0 | A |
Air Flow | Outdoor Unit | 5500 | m3 / h |
Sound Pressure Level at 1 m | Outdoor Unit | 60 | dB(A) |
Sound Power Level | Outdoor unit | 75 | dB(A) |
Refrigerant / Charge / Eq. CO2 | - | R32 / 3,50 / 2,36 | type / kg / t |
Additional Refrigerant | - | 35 | g / m |
Refrigerant Liquid Pipe | Diameter | 3/8 / 9,5 | inch / mm |
Refrigerant Gas Pipe | Diameter | 5/8 / 15,9 | inch / mm |
Max pipe length without additional refrigerant | - | 7,5 | m |
Maximum overall length of piping | - | 75 | m |
Max. Elevation | - | 30 | m |
Dimension (w x h x d) | Outdoor Unit | 990 × 960 × 370 | mm |
Package (w x h x d) | Outdoor Unit | 1153 × 1110 × 478 | mm |
Net / Gross Weight | Outdoor Unit | 94,0 / 103,0 | kg |
Operating Temperature Range | Cooling | - 20 ~ 52 | °C |
Operating Temperature Range | Heating | - 20 ~ 24 | °C |
Notes | The specification of products is subject to change based on further development of the units by the producer and can be changed without prior notice. Refer to rating label. |